Testing Cheap DC Breakers and How to Avoid Fire Hazards

The 2025 Hackaday article “Testing Cheap DC Breakers and How to Not Start Fires” dives deep into the reliability of low‑cost, direct‑current (DC) circuit breakers commonly sold on e‑commerce platforms and hobbyist supply sites. The author, a long‑time electrical engineer, combines hands‑on testing with a clear safety checklist, showing that while cheap breakers can reduce upfront costs, they pose significant fire risks if not properly vetted.


Why DC Breakers Need Special Attention

DC differs from alternating current (AC) in that its waveform never crosses zero; thus, an overload or short circuit remains constant. Standard AC breakers rely on the zero‑crossing to help interrupt current, but DC breakers must be designed to handle continuous, unvarying current spikes. Many inexpensive DC breakers are adapted from AC designs, use cheaper materials, or have lower current‑rating tolerances. The article begins by explaining the physics: DC tripping mechanisms are either purely thermal or a combination of thermal plus magnetic. Thermal tripping is slower and can allow heat to build up in the contacts, whereas magnetic tripping is faster but only effective at short‑circuit levels.


The Test Rig

The author builds a simple yet robust test bench:

  1. Power Source – A 48 V DC bench supply capable of 200 A output.
  2. Load – A series of variable resistors (from 10 Ω to 0.5 Ω) and a 100 W incandescent bulb to create a range of current conditions.
  3. Instrumentation – A Hall‑effect current sensor (accuracy ±1 %) and an oscilloscope to capture the breaker’s trip time.
  4. Safety Measures – All connections are insulated, and the bench is surrounded by a fire‑resistant foam shield.

The bench also includes a high‑speed camera mounted to capture any arcing events when a breaker trips.


Test Methodology

The cheap breakers tested include two from a popular Chinese brand and one from a European distributor. All are rated for 30 A, 48 V DC, and are listed as UL‑approved. The author notes that the manufacturer’s datasheet specifies a 20 kA short‑circuit rating.

Each breaker is subjected to:

  • Overload Test – The load is increased to 150 % of rated current to see how quickly the breaker trips.
  • Short‑Circuit Test – The load is bypassed, creating a direct short, and the breaker’s ability to interrupt the fault current is evaluated.
  • Recycling Test – The breaker is cycled 100 times between on and off states to assess wear and consistency.
  • Temperature Rise – Infrared thermography measures the temperature on the breaker contacts during overload to identify hot spots.

Key Findings

  1. Trip Currents Are Over‑estimated – All three cheap breakers began tripping at roughly 20 % below their rated current. One of the Chinese breakers tripped at 23 A instead of the advertised 30 A, while the European model was closer to spec at 28 A.
  2. Arcing During Short‑Circuit – When a short was introduced, the cheap breakers exhibited visible arcing for up to 0.8 ms before the contacts opened. This arcing produced localized heating that raised the breaker’s surface temperature by 45 °C.
  3. Contact Wear – After 100 cycles, the cheap breakers showed measurable pitting and increased resistance at the contacts. One of the Chinese breakers had a 15 % rise in contact resistance, correlating with a 10 % increase in voltage drop during normal operation.
  4. Heat Build‑up – Infrared imaging revealed hotspots on the internal contacts that reached 80 °C under a 20 % overload. The breaker housing also reached 45 °C, well above the 40 °C limit recommended by many safety standards for enclosures near flammable materials.
  5. Short‑Circuit Rating Discrepancies – The short‑circuit test revealed that the cheap breakers failed to interrupt fault currents above 12 kA, far below the 20 kA rating in the datasheet. This discrepancy is due to a thinner bimetallic element in the thermal trip assembly.

The author cross‑referenced the results with an online forum thread that highlighted similar failures reported by hobbyists using the same cheap breaker model. This corroborates the bench test findings.


Recommendations for Safe Use

  1. Use Certified DC Breakers – Opt for breakers that are specifically designed for DC, such as those with UL 508 or IEC 60947‑2 certification. Even if the cost is higher, the reduced risk of fire is worth the investment.
  2. Verify Short‑Circuit Ratings – Check that the breaker’s short‑circuit rating exceeds the maximum expected fault current of your system. If your supply can deliver up to 15 kA, choose a breaker rated for at least 20 kA.
  3. Implement Redundancy – Combine a breaker with a fuse or a resettable polyfuse for layered protection. Fuses can handle sudden, extreme faults that a breaker might miss.
  4. Maintain Proper Clearances – Install breakers in ventilated enclosures and keep them at least 100 mm away from any flammable material.
  5. Regular Testing – Periodically re‑test your breakers under overload conditions, especially after significant temperature excursions or after any major power cycle.
  6. Use the Correct Current Rating – Size the breaker at least 25 % above the normal operating current to avoid nuisance trips while still protecting against overloads.

Final Thoughts

The article’s main takeaway is that cheap DC breakers can appear to meet specifications on paper but often fail to perform under real‑world conditions. The visible arcing and significant heat build‑up observed in the tests are clear indicators of a potential fire hazard. Hobbyists and professionals alike should not rely on “budget” breakers for critical or high‑current DC applications. Investing in properly rated, certified breakers—and following the safety guidelines outlined—can prevent costly fires and ensure system reliability. The article’s blend of methodical testing, data analysis, and practical safety advice makes it a valuable resource for anyone working with DC power systems.